Product details

GCS low-voltage withdrawable type complete switchgear (hereinafter referred to as the "switch equipment") is my company to meet the requirements of the design unit and power users design developed in line with the national conditions, with high technical performance indicators and can adapt to power market development needs and can compete with the introduction of existing product low voltage draw-out switchgear.

This product has been widely used by power users.

Switchgear is suitable for power plant, petroleum, chemical, metallurgy, textile, high-rise building and other industries distribution system.

In large power plants, petrochemical systems and other places with high degree of automation and requiring computer interface, itis used as a low-voltage complete power distribution device for power distribution, centralized control of motors and reactive power compensation in power generation and power supply systems with three-phase AC frequency of 50(60)Hz, rated working voltage of 380V(400V), (660V) and rated current of 4000A or below.

The basic form of switchgear (see figure 1).

This product conforms to the standards of GB7251 low voltage switchgear and control equipment, JB/T9661 low voltage draw-off switchgear and IEC439 low voltage switchgear and control equipment.

Technical Parameter

Rated voltage of auxiliary circuit (V)



AC220、380(400)DC110、220

FN12-10

FZN25-12

Rated frequency (Hz)



50(60)

12

Rated insulation voltage (V)



660(1000)



Rated current (A)


horizontal bus

W4000




Vertical busbar (MCC)

1000

50

Rated short-time tolerable current of bus (kA/1 s)


50, 80

630

Rated peak tolerance current of bus (kA/ 0.1s)

105, 176

630

Power frequency test voltage (V/1min)


main circuit

2500

Not less than 100


ancillary circuit

1760

1250

generatrix


three-phase four-wire system

A. B、C、PEN

20/4;


Three phase five wire system

A. B、C、PE、N

Ground switch 20/2

level of protection



IP30、 IP40

50

11


Rated short-circuit making current (peak value)

50


12

combination

Fuse rated current

A

100

13

Electrical appliances

Rated transfer current

1500

2000

14


Rated short-circuit breaking current

kA

31.5

15


Equipped with fuse model


SQLAJ-12(XRNTa-10)

16

Mechanical life

Times

2000

10000

17

Auxiliary circuit 1min power frequency withstand voltage

kV

2

18

Working voltage of electric operating mechanism

V

Ac/dc 220;110

19

Protection level


IP2X

20

Dimensions (width x depth x height)

mm

650(850)x900x2000(2200)

The Use of Conditions

1.Temperature of ambient air: -5°C~+40 pairs;The average daily temperature shall not be higher than +35°C.
In case of excess, the capacity shall be reduced according to the actual situation.
2.Altitude: 2000m and below.
3.relative humidity: the maximum temperature of +40P is not more than 50%, at a lower temperature allowed to have a large relative humidity: such as +20P is 90%, should take into account the temperature changes may occasionally produce the impact of condensation.

4.The mounting incline shall not exceed5.and the whole group of cabinets is relatively flat (in line with GBJ232-82 standard).

5.Switchgear should be installed in places free from severe vibration and shock and not enough to cause undue corrosion ofelectrical components.
Note: users have special requirements, can negotiate with the company to solve.